Top Radar level sensor provider: When the cover above the closed metal cover is opened, the false signal disappears, the overall noise line decreases, and the echo curve decreases. After analysis, it is determined that the closed metal cover is the main cause of false signals, the radar level meter antenna is made of plastic, and the radar waves emitted by the antenna leak into the external environment. The closed metal shield is used to cover the instrument, and the leaked radar wave signal is received by the antenna after several reflections inside the shield, generating a false level. Therefore, the metal shield was modified to a ring-shaped non-sealed shield at a later stage, and the radar level meter jump was significantly reduced. See even more details on radar level sensor.
Radar level measurement technology symbolizes precision and innovation in industrial level sensing. Its non-contact operation, resilience in challenging environments and ability to handle measurement scenarios have earned it a reputation. Furthermore, with the integration of IIoT capabilities and temperature compensation features radar sensors continue to evolve and make contributions to advancing processes. As automation and digitalization become more widespread across industries, radar level measurement continues to be a technology that ensures efficiency, safety and reliability in their operations. By relying on radar sensors as guardians, industries can confidently navigate the intricacies of level measurement with unwavering precision.
Power supply and output signal, the power supply has 220 V A C, 24 VDC, and the two-wire or four-wire system can be selected according to the needs. Output signal 4 ~ 20 mA DC or digital signal, select the appropriate model according to the needs. The above are all factors that need to be considered when selecting a radar level transmitter. The essence of the details is a serious attitude and a scientific spirit. I hope that every user can choose a suitable radar level meter.
The electromagnetic wave emitted during measurement can pass through the vacuum, no transmission medium is required, and the anti-interference ability is strong, and it is not affected by temperature, wind, water vapor, water mist, rain, etc. It can be used for liquid level measurement of almost all liquids, and can be continuously measured on-line unattended. Large measurement range, high precision, mature technology and stable performance.
Level Measurement Solutions for Deaerators: With proper level control and instrumentation, every part of the steam generation cycle can be managed for optimal efficiency. Deaerator Functions: The deaerator serves as an “open” type heat exchanger with its primary function being the removal of oxygen and other corrosive gases from the boiler feedwater. This is accomplished using steam, which can give up about 970 Btu per pound, to support the deaeration process as well as preheat boiler feedwater.
In addition, some silos in cement plants are very high, such as homogenizing silos of 50cm. It takes time and energy to board high silos to debug radar, so it is recommended to choose HART handheld operators that can be debugged remotely in the central control room. In the central control room, the range and other basic parameters can be set, and the radar echo waveform can be observed, and the waveform can be used for remote diagnosis and debugging, greatly reducing the on-site work intensity of the staff, to avoid the risk of climbing operation. The smart radar level gauge commonly used at present also has a function similar to “driving recorder”, that is, when the material surface mutation occurs on the scene, it can capture the radar echo waveform at that time, which is very useful for debugging the silo under complex conditions.
As one of the most professional magnetic level indicators manufacturers in China,Guangdong Kaidi Energy Technology Co., Ltd. provides customized solutions for a range of industrial automation process applications,such as mechanical float level indicator.We specialized in radar level gauge, fork type level switch,etc. These were implemented successfully, and KAIDI magnetic level gauge manufacturers products,such as radar level meter, magnetic level indicators, can be used in many different industries such as food & beverage, water, energy, pharmaceutical etc. Find extra info at https://www.kaidi86.com/. OEM Service-can be customized according to the application of customer,such as level gauge,level switch and level indicator.
Thermal interference. During the operation of the thermal power plant, its thermal equipment will generate a lot of heat, causing changes in the surrounding instruments and ambient temperature. This is what we call thermal interference. These disturbances can affect the components of the magnetrol radar level gauge and further create problems such as inaccurate measurements. Light interference, light interference mainly exists in semiconductor components. Many components used to control instruments are made of semiconductor materials whose conductivity changes under the influence of light. This will affect the normal use of the radar level gauge.
When the distance between the liquid level of the measured medium and the electromagnetic wave transmitter is less than 4m, the guided wave radar is selected. If the distance between the liquid level of the measured medium and the electromagnetic wave transmitter is greater than 4m and less than 35m, select the guided wave radar with the guided wave cable. When the distance between the liquid level of the measuring medium and the electromagnetic wave transmitter is greater than 35m, or when the liquid level of the measuring medium is high temperature, high viscosity or solid liquid level, the air-shooting radar should be selected.
Working principle: Tube in the liquid level meter has a magnetic float, float design, according to the proportion of medium float magnet steel and container liquid level at the same level, wholesale liquid level gauge in a semiconductor magnetel liquid level gauge sensor LED display scale, and orderly arranged from top to bottom, and LED module corresponding to the magnetic field magnetic sensor, the magnetic semiconductor, triggering the corresponding digital circuit, liquid level above the red LED display, The LED below the liquid level gauge is displayed in green, the red in gas phase, and the green in liquid phase. The red-green junction is the actual liquid level in the container.